ASTM E1300 09a Example 3: Double glazed unit, 1/4 in tempered over 5/16 in laminated

Find the load resistance of a double glazed unit of 59.84 by 74.80 in with a 1/4 in tempered lite and a 5/16 in laminated lite, under a 125.3 psf long duration load.

Inputs

Long dimension, a
74.80 in
Short dimension, b
59.84 in
Construction
Insulating, double
Lite 1
1/4 in FT
Lite 2
laminated 5/16 in HS
Load share form
LS multipliers
Unit type
Double glazed
Glass type
Fully tempered (FT)
Load duration
Long (30 day)
Design load, p
125.31 psf
Allowable deflection, w_allow
b/100

Insulating glass

Construction
Insulating glass, double glazed unit of monolithic lites
Lite 1
1/4 in, fully tempered (FT)
Lite 1 thickness used
0.219 in (Table 4 minimum)
Lite 2
5/16 in, heat strengthened (HS)
Lite 2 plies
5/32 in + 5/32 in
Lite 2 interlayer thickness
0.030 in
Lite 2 designation
5/16 in (sum of ply minimum thicknesses and interlayer, 0.328 in, interlayer at most 0.060 in; E1300 09a 3.2.4.2)
Lite 2 thickness used
0.292 in (Table 4 minimum of the designation)

Calculations

Support
Four sides, double glazed insulating glass
Long dimension, a
74.80 in
Short dimension, b
59.84 in
Non factored load (NFL)
52.22 psf
Glass type factor (GTF)
1.90
Load resistance (LR)
140.90 psf
Lite 1: 1/4 in, fully tempered (FT)
Non factored load (NFL)
36.81 psf, E1300 chart
Glass type factor (GTF)
2.85
Load share LS
1.63, Table 5
Load resistance of the lite (LR)
171.01 psf
Share of the design load (p·LSF)
76.88 psf
Load times area squared at the share, (p·LSF)·A²
74.29 kip·ft²
Load resistance of the lite, short duration load
471.42 psf (GTF 3.80, Load share LS 3.37)
Load resistance of the lite, long duration load
171.01 psf (GTF 2.85, Load share LS 1.63)
Deflection of the lite, w
1.134 in, Appendix X2
p̂, x = ln(ln p̂) (at the share of the load)
448.05, 1.81
Modulus of elasticity, E
10,400 ksi
r0, r1, r2 (X2, R capped at 5)
−2.69, 2.01, 0.21
Lite 2: laminated, designation 5/16 in, heat strengthened (HS)
Laminated glass chart
E1300 09a 6.11 to 6.14, Fig A1.29
Non factored load (NFL)
52.22 psf, E1300 chart
Glass type factor (GTF)
1.90
Load share LS
1.42, Table 5
Load resistance of the lite (LR)
140.90 psf, governs the unit
Share of the design load (p·LSF)
88.25 psf
Load times area squared at the share, (p·LSF)·A²
85.28 kip·ft²
Load resistance of the lite, short duration load
140.90 psf (GTF 1.90, Load share LS 1.42)
Load resistance of the lite, long duration load
169.07 psf (GTF 1.25, Load share LS 2.59)
Deflection of the lite, w
0.918 in, Appendix X2
p̂, x = ln(ln p̂) (at the share of the load)
162.15, 1.63
Modulus of elasticity, E
10,400 ksi
r0, r1, r2 (X2, R capped at 5)
−2.69, 2.01, 0.21
E1300 procedure
E1300 09a 6.10, double glazed insulating glass, four sides
Glass type factors
E1300 09a Table 2, Lite 1 FT with Lite 2 HS; E1300 09a Table 3, Lite 1 FT with Lite 2 HS
Load share source
E1300 09a Table 5, printed values (LS multipliers)
Long duration load share source
E1300 09a Table 6 (monolithic lite with laminated lite), printed values
Thickness cubed of each lite
0.010 in³, 0.025 in³
Aspect ratio, AR
1.25
Load times area squared, whole unit, p·A²
121.09 kip·ft²
Governing lite
Lite 2, load resistance 140.90 psf
Largest lite deflection, w (Lite 1)
1.13 in
Allowable deflection
w_allow = b/100 = 59.84/100 = 0.60 in
Deflection to thickness ratio, w/t
5.18

Load share, LS multipliers: E1300 Table 5, E1300 09a Table 5. This is the E1300 value.

Lite 1 non factored load (NFL): E1300 chart, E1300 09a Fig A1.6. This is the E1300 value.

Lite 1 deflection: E1300 Appendix X2. E1300 gives no deflection method for insulating glass.

Lite 2 non factored load (NFL): E1300 chart, E1300 09a Fig A1.29. This is the E1300 value.

Lite 2 deflection: E1300 Appendix X2. E1300 gives no deflection method for insulating glass.

Non factored load (NFL) chart
0501001500200040000501000100020003000Long dimension, a (in)Long dimension, a (mm)Short dimension, b (in)Short dimension, b (mm)20.931.352.2146NFL = 52.22 psf

Contours: NFL in psf, labelled on the chart. 1/4 in laminated glass, four sides simply supported, 3 second load.

Deflection chart
02004000501001500.00.51.01.502040Load times area squared, p·A² (kip·ft²)Load times area squared, p·A² (kN·m²)Deflection, w (in)Deflection, w (mm)AR 1AR 2AR 3AR 4AR 5w = 1.13 in

Curves: center of glass deflection w for aspect ratio (AR) 1 to 5; highlighted: this aspect ratio.

Non factored load (NFL) chart, Lite 1
0501001500200040000501001500100020003000Long dimension, a (in)Long dimension, a (mm)Short dimension, b (in)Short dimension, b (mm)15.720.931.383.5104NFL = 36.81 psf

Contours: NFL in psf, labelled on the chart. 1/4 in glass, four sides simply supported, 3 second load.

Glass sizes where the NFL is above 210 psf, result outside the scope of ASTM E1300.

Deflection chart, Lite 1
05010015002040600.00.51.00102030Load times area squared, p·A² (kip·ft²)Load times area squared, p·A² (kN·m²)Deflection, w (in)Deflection, w (mm)AR 1AR 2AR 3AR 4AR 5w = 1.13 in

Curves: center of glass deflection w for aspect ratio (AR) 1 to 5; highlighted: this aspect ratio.

Point at the share of the load on this lite, (p·LSF)·A².

Redrawn by GlassLoad.com based on the ASTM E1300 09a Figure A1.29 printed chart; results vary by about 0.1 percent.

Redrawn by GlassLoad.com based on the ASTM E1300 09a Figure A1.6 printed chart; results vary by about 1.0 percent.

Outputs

Strength PASS. Deflection FAIL.

Probability of breakage at the design load: not available for insulating glass.

Strength: p = 125.31 psf ≤ LR = 140.90 psf; p/LR = 0.89.

Deflection at CoG: w = 1.13 in > w_allow = 0.60 in (b/100, four edges supported).

CoG: center of glass

GlassLoad.com 140.9 psf, printed 141 psf. The standard printed 6.75 kPa. The printed example is a horizontal skylight and subtracts the glass weight. GlassLoad.com calculated the unit as vertical glass, so the glass weight is not subtracted. The printed value is the one before the glass weight.

Notes

W7
E1300 gives no deflection method for IG, so w of each lite is approximate, from Appendix X2 at the share of p that lite carries. Where deflection governs, verify it by an independent method.
W25
Appendix X1 is evaluated at the thickness t, the Table 4 minimum of the designation and at the share of p that lite carries, which treats the plies as one lite and ignores the interlayer under a long duration load, so w can be understated. Where deflection governs, verify it by an independent method.
W6
No Pb is reported for IG, because E1300 gives Pb of IG only in the analytical procedure of E1300 24 7.3.3, which GlassLoad.com does not run. Where Pb is required, calculate it by that procedure.
W18
A laminated lite of two plies with an interlayer is read as its thickness designation by E1300 3.2.4.2. For a long duration load, E1300 6.11 to 6.14 gives the unit the lowest of four values, so check that the designation matches your laminate.
W27
Load sharing uses the load share factors LS, which are approximate, and pressure changes in the air space from temperature and altitude are not included. If the unit is at high altitude or sees large temperature changes, check the air space pressure separately.

More examples are on the E1300 09a page and on the examples page. Open the calculator to run your own check.